Digital Output 1 and Digital Output 2

Itron water modules are compatible with all sizes of Digital Output 1 and Digital Output 2 registers and CMAG/EMAG meters.

Cadillac meters are approved for use in the configurations described in Table 12 and Table 13.

Table 12 Itron Configurations: Cadillac Meter (Flow Units: Gal/Min and Gallons) for 60WP and 100WP/+

Size

Display 1

Display 2

R1

DO1 function

Count rate

Pulse mode

Pulse width

0.5” thru 6”

gal/min

Count F

5 m/s

PLS Out

10 gal

Auto

100 ms

8” thru 24”

gal/min

Count F

5 m/s

PLS Out

100 gal

Auto

100 ms

28” thru 36”

gal/min

Count F

5 m/s

PLS Out

1000 gal

Auto

100 ms

Table 13 Itron Configurations: Cadillac Meter (Flow Units: Ft3/Min and Ft3) for 60WP and 100WP/+

Size

Display 1

Display 2

R1

DO1 function

Count rate

Pulse mode

Pulse width

0.5” thru 20”

gal/min

Count F

5 m/s

PLS Out

10 Ft3

Auto

100 ms

24” thru 36”

gal/min

Count F

5 m/s

PLS Out

100 Ft3

Auto

100 ms

Additionally:

  • R1, which is meter flow span setting, is determined by using approximately five m/s as maximum system design velocity.

  • When Pulse Mode is set to Auto, the default for Pulse Width becomes 100 ms.

  • Count Rate (Pulse scaling factor) can always be larger than what is listed for any given meter size. It cannot be smaller and must meet 100 ms pulse width.

  • Pulser ERTs must be programmed to 100ms Pulse seven-digit driver.